What is the maximum IT load supported by FusionModule2000 integrated UPS?
- A . 125KW
- B . 150KW
- C . 75KW
- D . 50KW
Which of the following voltage systems does UPS5000-E support? (Multiple choice)
- A . 380V
- B . 480V
- C . 415V
- D . 400v
FusionModule800 has the function of self-starting when incoming calls for civil air conditioners.
- A . True
- B . False
Which of the following statements about micromodules and fire protection systems are correct? (Multiple choice)
- A . When a fire alarm occurs in the channel, ECC800 provides a passive 1,000-point signal to the data center fire host to warn
- B . ECC800 can control the skylight to flip and the fire sprinkler to spray fire gas
- C . The data center fire host provides passive dry contact signals to ECC800, and ECC800 can identify fire alarm information
- D . ECC800 can control the module and the building fire protection linkage
12V battery cells, which of the following voltages are normal operating voltages that they can accept? (Multiple choice)
- A . 13V
- B . 14.1V
- C . 14.52V
- D . 10.02V
When the Fusionmodule2000 single-row cabinet is used, the configuration of sliding doors/electric doors is not supported.
- A . True
- B . False
The load is 120kW. UPS5000-S is used to meet N+2 modular redundant configuration. The configurable model is () kVA.
- A . 160kVA
- B . 200kVA
- C . 240kVA
- D . 250kVA
Huawei 25KW half cabinet variable frequency air-cooled air conditioner, which of the following description is correct? (Multiple choice)
- A . The capacity calculation of a single air conditioner with UPS is 1.2* 1.732* full load current*380*0.8/0.9
- B . The capacity calculation of a single air conditioner with UPS is 1.2*5*1.732*full load current*380*0.8/0.9
- C . The UPS capacity requirement for a single air conditioner is 15.8kVA. If UPS5000E is used, at least one 25kVA power module is required.
- D . The UPS capacity requirement for a single air conditioner is 79.0kVA. If UPS5000E is used, at least two 40kVA power modules are required.
- E . If a group of air conditioners is connected to a UPS system, then the number of air conditioners running simultaneously needs to be multiplied by the number of air conditioners on the basis of a single UPS. For example, for a 5+1 cold backup configuration, the total UPS capacity requirement needs to be multiplied by 5 based on the UPS capacity requirement of a single air conditioner .
What are the optional accessories of UPS5000-E (25-75kVA)? (Multiple choice)
- A . Earthquake-resistant components
- B . Air outlet components
- C . Ambient temperature and humidity sensor
- D . BSC line system
The self-developed air conditioning control system has a visual group control network and supports up to 32 units
- A . True
- B . False